Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 44

Advertising
background image

5-14

ControlNet Communications Module

Step 9.

Enter the input and output size for the node on the
network. The number of words selected depends on the
I/O to be communicated with the node. In this example,
the Node 2 SP600 is set for all I/O enabled which equates
to 10 words of I/O (table 5.1).

Important: The size of the Reference (Ref/Fdbk Size (7)) and

Datalinks (Datalink Size (8)) will affect the size you
configure for the network I/O. For example, 32-bit
Datalinks requires twice as many words as 16-bit
Datalinks. Depending on your application, the
configured I/O size may vary.

Figure 5.19 – Integer Files for ControlNet Communications Screen

Table 5.1 – Input/Output Table

Words

Input to PLC-5C

Output to PLC-5C

0-1

Logic Command /
Reference

Logic Status /
Feedback

2-3

Datalinks A1 & A2 Out

Datalinks A1 & A2 In

4-5

Datalinks B1 & B2 Out

Datalinks B1 & B2 In

6-7

Datalinks C1 & C2 Out

Datalinks C1 & C2 In

8-9

Datalinks D1 & D2 Out

Datalinks D1 & D2 In

SP600