ControlNet Communications Module
8.1.3 NET A and B Together
Table 8.3 – NET A and B Together: State Definitions
Status
Cause
Corrective Actions
Both LEDs
are off
A reset occurred or
there is no power.
•
Apply power to the module.
Both LEDs
are steady
red
A link interface
failed.
•
Check media for broken cables,
loose connectors, missing
terminators, etc.
•
Power cycle or reset the
module. If the problem persists,
contact Rockwell Automation
support.
LEDs are
alternating
red/green
The module is in
self-test mode.
•
No action required. The module
will exit this mode when the
self-test is completed.
LEDs are
alternating
red/off
There is a bad
configuration.
•
Verify that all node addresses
are unique.
•
Check the module’s
configuration.
•
Check media for broken cables,
loose connectors, missing
terminators, etc.
•
Power cycle or reset the
module.