ControlNet Communications Module

8.1.3 NET A and B Together

Table 8.3 – NET A and B Together: State Definitions

Status

Cause

Corrective Actions

Both LEDs
are off

A reset occurred or
there is no power.

Apply power to the module.

Both LEDs
are steady
red

A link interface
failed.

Check media for broken cables,
loose connectors, missing
terminators, etc.

Power cycle or reset the
module. If the problem persists,
contact Rockwell Automation
support.

LEDs are
alternating
red/green

The module is in
self-test mode.

No action required. The module
will exit this mode when the
self-test is completed.

LEDs are
alternating
red/off

There is a bad
configuration.

Verify that all node addresses
are unique.

Check the module’s
configuration.

Check media for broken cables,
loose connectors, missing
terminators, etc.

Power cycle or reset the
module.