ControlLogix Applications

7-9

Step 11. The Requested Packet Interval (RPI) schedules the

connection to move data to or from the module at least
this often or the connection will fail with the RPI Not Valid
error. Set this value to 5 ms or greater, and click Next>
(figure 7.12).

Important: The RPI time must be set greater than or equal to the

Network Update Time (NUT).

Figure 7.11 – Module Properties: ControlNet Module Parameters

SP600_02

Figure 7.12 – Module Properties: RPI Selection