Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 140

Advertising
background image

C-24

ControlNet Communications Module

The PLC data in this example is for a Set_Attributes_Scattered of
SP600 parameters; Accel Time 1 (140), Decel Time 1 (142), and
Jog Speed (100) to a device at node address 1.

Request Data for Set_Attributes_Scattered

Response Data for Set_Attributes_Scattered

Word

Value

(hex)

Description

0

008C

Parameter Number 140 (8C Hex)

1

0032

Value = 50 (32 hex) = 5.0 seconds

2

0000

3

008E

Parameter Number 142 (8E hex)

4

0032

Value = 50 (32 hex) = 5.0 seconds

5

0000

6

0064

Parameter Number 100 (64 hex)

7

0064

Value = 100 (64 hex) = 10.0 Hz

8

0000

Word

Value

(hex)

Description

0

008C

Parameter Number 140 (8C hex)

1

0000

2

0000

3

008E

Parameter Number 142 (8E hex)

4

0000

5

0000

6

0064

Parameter Number 100 (64 hex)

7

0000

8

0000

Advertising