C-24
ControlNet Communications Module
The PLC data in this example is for a Set_Attributes_Scattered of
SP600 parameters; Accel Time 1 (140), Decel Time 1 (142), and
Jog Speed (100) to a device at node address 1.
Request Data for Set_Attributes_Scattered
Response Data for Set_Attributes_Scattered
Word
Value
(hex)
Description
0
008C
Parameter Number 140 (8C Hex)
1
0032
Value = 50 (32 hex) = 5.0 seconds
2
0000
3
008E
Parameter Number 142 (8E hex)
4
0032
Value = 50 (32 hex) = 5.0 seconds
5
0000
6
0064
Parameter Number 100 (64 hex)
7
0064
Value = 100 (64 hex) = 10.0 Hz
8
0000
Word
Value
(hex)
Description
0
008C
Parameter Number 140 (8C hex)
1
0000
2
0000
3
008E
Parameter Number 142 (8E hex)
4
0000
5
0000
6
0064
Parameter Number 100 (64 hex)
7
0000
8
0000