Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 138

Advertising
background image

C-22

ControlNet Communications Module

The PLC data in this example is for a Get_Attributes_Scattered of
SP600 parameters; Output Freq (1), Output Current (3), and Ouptut
Voltage (6) from a device at node address 1.

Request Data for Get_Attributes_Scattered

Response Data for Get_Attributes_Scattered

Word

Value (hex)

Description

0

001

Parameter Number 1

1

0000

Pad Word

2

0000

Pad Word

3

0003

Parameter Number 3

4

0000

Pad Word

5

0000

Pad Word

6

0006

Parameter Number 6

7

0000

Pad Word

8

0000

Pad Word

Word

Value

(hex)

Description

0

0001

Parameter Number 1

1

0258

Value = 600 (258 hex) = 60.0 Hz

2

0000

3

0003

Parameter Number 3

4

0001

Value = 1 (1 hex) = 0.1A

5

0000

6

0006

Parameter Number 6

7

0864

Value = 2148 (864 hex) = 214.8V AC

8

0000