Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual
Page 138
Advertising
C-22
ControlNet Communications Module
The PLC data in this example is for a Get_Attributes_Scattered of
SP600 parameters; Output Freq (1), Output Current (3), and Ouptut
Voltage (6) from a device at node address 1.
Request Data for Get_Attributes_Scattered
Response Data for Get_Attributes_Scattered
Word
Value (hex)
Description
0
001
Parameter Number 1
1
0000
Pad Word
2
0000
Pad Word
3
0003
Parameter Number 3
4
0000
Pad Word
5
0000
Pad Word
6
0006
Parameter Number 6
7
0000
Pad Word
8
0000
Pad Word
Word
Value
(hex)
Description
0
0001
Parameter Number 1
1
0258
Value = 600 (258 hex) = 60.0 Hz
2
0000
3
0003
Parameter Number 3
4
0001
Value = 1 (1 hex) = 0.1A
5
0000
6
0006
Parameter Number 6
7
0864
Value = 2148 (864 hex) = 214.8V AC
8
0000