Viewing the module configuration, 8 viewing the module configuration – Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 28

Advertising
background image

4-8

ControlNet Communications Module

Set Reset Module (9) to Reset Module. See figure 4.7.

When you enter 1 (Reset Module), the module will be immediately
reset. When you enter 2 (Set Defaults), the module will set all
module parameters to their factory-default settings. The value of this
parameter will be restored to 0 (Ready) after the module is reset or
resetting the defaults. The module should be reset after performing
a “Set Defaults.”

4.8

Viewing the Module Configuration

The parameters in table 4.4 provide information about how the
module is configured. You can view these parameters at any time.

Figure 4.7 – Reset Screen on an LCD OIM

Port 5 Device

RECOMM-CNET

Parameter #: 9
Reset Module

1

Reset Module

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Table 4.4 – Module Configuration Status Parameters

No.

Name and Description

Details

01

DPI Port
Port to which the module is connected. This will
usually be port 5.

Default:

5

Minimum:

0

Maximum:

7

Type:

Read Only

02

DPI Data Rate
Data rate used by the drive. This data rate is set in
the drive and the module detects it.

Default: 0 = 125 K
Values 0 = 125 K
1 = 500 K
Type: Read Only

04

CN Addr Act
The actual network node address.

Default: 2
Minimum: 1
Maximum: 99
Type: Read Only

06

CN Rate Act
The actual network data rate.

Default: 0 = 5 Mbps
Values: 0 = 5 Mbps
Type: Read Only

07

Ref/Fdbk Size
Size of the Reference/Feedback. The drive
determines the size of the Reference/Feedback.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read Only

08

Datalink Size
Size of each Datalink word. The drive determines
the size of Datalinks.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read Only