8-2

ControlNet Communications Module

8.1.1 DRIVE Status Indicator

Table 8.1 – DRIVE Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module is not
powered or is not
connected properly to
the drive.

Securely connect the module
to the drive using the ribbon
cable.

Apply power to the drive.

Flashing
Red

The module is not
receiving a ping
message from the
drive.

Verify that cables are
securely connected.

Cycle power to the drive.

Solid
Red

The drive has refused
an I/O connection from
the module.

Another DPI peripheral
is using the same DPI
port as the module.

Important: Cycle power to the
product after making any of the
following corrections:

Verify that all DPI cables are
securely connected and not
damaged. Replace cables if
necessary.

Verify that the DPI Host
supports Datalinks.

Configure the module and
DPI Host to use a Datalink
that is not already being
used by another peripheral.

Orange

The module is
connected to a product
that does not support
Reliance Electric DPI
communications.

Connect the module to a
product that supports
Reliance Electric DPI
communications (for
example, SP600 drives).

Flashing
Green

The module is
establishing an I/O
connection to the drive.

No action. Normal behavior if
no DPI I/O is enabled.

Solid
Green

The module is properly
connected and is
communicating with the
drive.

No action.