Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 66

Advertising
background image

6-16

ControlNet Communications Module

Set Attributes Scattered Example request and response Data:

Request Data

Response Data

A Get Attribute Single message is used to read a single parameter
(figure 6.11).

A Service Code of “E” indicates the Get_Attribute_Single service
(see page C-20, Common Services).

An Instance Number of “1” indicates Drive Parameter 1 will be
accessed (see page C-16, Instances).

An Attribute Number of “9” indicates the Parameter Value
Attribute will be accessed (see page C-17, Instance Attributes).

N13:0

45

Parameter Number = 45

N13:1

50

Value = 0.50HP

N13:2

0

(Pad Word)

N13:3

44

Parameter Number = 44

N13:4

1740

Value = 1740RPM

N13:5

0

(Pad Word)

N13:6

43

Parameter Number = 43

N13:7

600

Value = 60.0Hz

N13:8

0

(Pad Word)

N13:9

42

Parameter Number = 42

N13:10

16

Value = 1.6Amps

N13:11

0

(Pad Word)

N14:0

45

Parameter Number = 45

N14:1

0

(Pad Word)

N14:2

0

(Pad Word)

N14:3

44

Parameter Number = 44

N14:4

0

(Pad Word)

N14:5

0

(Pad Word)

N14:6

43

Parameter Number = 43

N14:7

0

(Pad Word)

N14:8

0

(Pad Word)

N14:9

42

Parameter Number = 42

N14:10

0

(Pad Word)

N14:11

0

(Pad Word)

Advertising