5-18
ControlNet Communications Module
Step 15. Enter a file name and click Save. The project is now
saved for future use.
5.1.3 Verifying Network Properties
In the Network menu, select Properties to display the ControlNet
dialog box (figure 5.26). Verify:
•
The number in the Max Scheduled Address field is higher than
or equal to the highest node number that will perform I/O
messaging.
•
The number in the Max Unscheduled Address field is higher
than or equal to the highest node number on the network.
•
The correct type of media redundancy is selected in the Media
Redundancy field.
Important: The value in the Network Update Time (ms) field is
5 ms or greater. Do not set lower than 5 ms. The NUT
must be set equal or lower than the RPI times set for
the devices on the network.
Figure 5.25 – Save As File Box
RECOMM-CNET Example.XC