5-12
ControlNet Communications Module
Step 6.
If the On-line / Off-line Mismatch dialog box appears, click
OK to use the on-line data (figure 5.16). If prompted to
save, save the data (figure 5.17).
Important: During the save process, RSNetWorx will execute the
browse function. Allow RSNetWorx to complete the
browse (1-99 nodes), even if you already see the entire
network. Canceling the browse early may cause an
improper scheduling of I/O.
Step 7.
Right-click on the controller’s icon (PLC-5C) and select
SCANlist Configuration. The Scanlist Configuration
screen (figure 5.18), is used to configure the controller to
communicate with the nodes.
Figure 5.16 – Online / Offline Mismatch Dialog Box
Figure 5.17 – Save Data Screen
RECOMM-CNET Example.XC