Register object, C.2 register object – Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 120

Advertising
background image

C-4

ControlNet Communications Module

C.2 Register Object

Class Code

Instances

Class Attributes

Hexadecimal

Decimal

0x07

7

Instance

Description

1

All I/O data being read from the DPI device (read-only)

2

All I/O data written to the DPI device (read/write)

3

Logic Status and Feedback data (read-only)

4

Logic Command and Reference data (read/write)

5

Datalink A (input data from device to scanner) (read only)

6

Datalink A (output data from scanner to device) (read/write)

7

Datalink B (input data from device to scanner) (read only)

8

Datalink B (output data from scanner to device) (read/write)

9

Datalink C (input data from device to scanner) (read only)

10

Datalink C (output data from scanner to device) (read/write)

11

Datalink D (input data from device to scanner) (read only)

12

Datalink D (output data from scanner to device) (read/write)

13

Logic Status and Feedback Data (read-only)

14

Mask

1

(read/write)

1

The mask command word is set to the value of the first word of the data
where there are ones in the second word of the data. Command = (word
1 and not word 2) or (word 1 and word 2). This only controls specified bits
in the Logic Command data to the DPI product and does not change the
Reference value.

Attribute

ID

Access

Rule

Name

Data Type

Description

100

Set

Control Timeout UINT

Control timeout in
seconds