Using the lcd oim to configure the module, Setting the node address, 2 using the lcd oim to configure the module – Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 22: 3 setting the node address

Advertising
background image

4-2

ControlNet Communications Module

4.2

Using the LCD OIM to Configure the
Module

Use the procedure in figure 4.1 to access the parameters on the
ControlNet module using the LCD OIM. If you are unfamiliar with
the operation of the LCD OIM, refer to the SP600 AC Drive User
Manual (D2-3485) for more information.

4.3

Setting the Node Address

If the node address switches are set to “00”, the value of CN Addr
Cfg (3) determines the node address.

Step 1.

Set the value of CN Addr Cfg (3) to a unique node
address.

Step 2.

Reset the module. Refer to section 4.7.3, Resetting the
Module.

Figure 4.1 – Accessing the ControlNet Parameters using the LCD OIM

P0: SP600

> >

Auto

Stopped

Main Menu

Device Select

Use to select

R E C O M M - C N E T .

P0: SP600

> >

Auto

Stopped

P5: RECOMM-CNET

> >

Auto

Stopped

Main Menu

Parameters

Device: Port 0

SP600

R E C O M M - C N E T

Monitor

Lang

Edit the ControlNet
parameters using the
same techniques as for
drive parameters.

Use to highlight

Device Select icon

Figure 4.2 – ControlNet Node Address Screen on an LCD OIM

Port 5 Device

RECOMM-CNET

Parameter #: 3
CN Addr Cfg

02

0 <> 99

Default = 02