1 changing the fault action – Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual

Page 26

Advertising
background image

4-6

ControlNet Communications Module

4.7.1 Changing the Fault Action

Set the values of Comm Flt Action (10) and Idle Flt Action (11) to
the desired responses as shown in table 4.2. See figure 4.6 for
sample LCD OIM Fault Action screens.

Changes to these parameters take effect immediately. A reset is not
required.

Table 4.2 – Selections for Drive Response to Communication Fault

Value

Action

Description

0

Fault (default)

The drive is faulted and stopped
(Default).

1

Stop

The drive is stopped, but not
faulted.

2

Zero Data

The drive is sent 0 for output data
after a communications disruption.
This does not command a stop.

3

Hold Last

The drive continues in its present
state.

4

Send Flt Cfg

The drive is sent the data that you
set in the fault configuration
parameters, Flt Cfg Logic (15)
through Flt Cfg D2 In (24).

Figure 4.6 – Fault Action Screens on an LCD OIM

Port 5 Device

RECOMM-CNET

Parameter #: 10
Comm Flt Action

0

Fault

Port 5 Device

RECOMM-CNET

Parameter #: 11
Idle Flt Action

0

Fault