Rockwell Automation RECOMM-CNET ControlNet Communications Module User Manual
Page 84

7-16
ControlNet Communications Module
Parameter Settings for the Sample Program
Logic Command/Status Words
These examples use the Logic Command word and Logic Status
word for SP600 drives. Refer to Appendix D, Logic Command/
Status Words to view these. The definition of the bits in these words
may vary if you are using a different DPI product. Refer to the
documentation for your drive.
Table 7.1 – Parameter Settings for the Sample Program
Device
Parameter
Name
Value
Description
SP600 Drive
90
Speed Ref A Sel
22
‘Network’ (RECOMM-CNET)
300
Data In A1
140
Points to 140 (Accel Time 1)
301
Data In A2
142
Points to 142 (Decel Time 1)
302
Data In B1
100
Points to 100 (Jog Speed)
303
Data In B2
155
Points to 155 (Stop Mode A)
310
Data Out A1
140
Points to 140 (Accel Time 1)
311
Data Out A2
142
Points to 142 (Decel Time 1)
312
Data Out B1
100
Points to 100 (Jog Speed)
313
Data Out B2
155
Points to 155 (Stop Mode A)
13
DPI I/O Cfg
xxx1 1111
Enables Cmd/Ref, Datalinks A-D
RECOMM-CNET
25
M-S Input
xxx1 1111
Configures the I/O Data to be
transferred from the network to the
drive.
26
M-S Output
xxx1 1111
Configures the I/O Data to be
transferred from the drive to the
network.