HEIDENHAIN MSE 1000 User Manual

Page 141

Advertising
background image

Troubleshooting

Application errors

Operating Instructions

141

Error

Cause

Corrective action

Duplicate IP Address

More than one module has the
same IP address.

Clearing the error will cause the
error to go away but any resulting
module chain will not be usable until
the problem is corrected.

DHCP addressing:

Restore factory defaults.

Static addressing:

Uninstall one of the modules with

the duplicate IP address from the

module chain.

Change the IP address of the other

module to a unique value.

Reinstall the removed module.

Error

A Query failed.

A Communication error and the
IP address of the module will
displayed.

Power cycle the module chain.

Refer to "Power cycling", page 33.

Perform a Broadcast.

Refer to "Network troubleshooting",

page 151.

Could not create the MSE 1000

module chain via broadcasting

A Broadcast failed.

Verify the network connection is

connected.

Verify power to the modules is on.

Verify the workstation IP address.

Verify the workstation netmask.

Verify the broadcast netmask.

Verify the workstation port.

Power cycle the module chain.

Refer to "Power cycling", page 33.

Wait for the Network bus LED to

flash 2/sec on all modules.

Perform a Broadcast.

Refer to "Network troubleshooting",

page 151.