Commissioning and preparing to measure

Network configuration

74

Operating Instructions

CAUTION

Observe the power consumption ratings of the modules and any devices connected
to a module. Insert an additional power supply module as required. Refer to "Module
specifications", page 158
.

Turn the power on.

The power LED's on each module should light solid green. Network LED's initially
flash green five times per second when waiting for DHCP to assign an IP address.

Wait for the Network LED to flash green twice per second on all modules.

Perform a broadcast. Refer to Broadcast"", page 67.

Click the «OK» button in the dialog box when asked to switch to static addressing.

Turn the power off.

Install up to ten more modules into the module chain.

Turn the power on.

Wait for the Network LED to flash green twice per second on all modules.

Perform a broadcast.

Click the «OK» button in the dialog box when asked to switch to static addressing.

Repeat turning the power off, installing up to ten modules, turning the power on,
broadcasting, and switching to static addressing until all modules in the module
chain have a unique IP address.