R status data – ProSoft Technology PLX8X-MNET-61850 User Manual

Page 103

Advertising
background image

PLX8x-MNET-61850 ♦ Communication Gateway

Diagnostics and Troubleshooting

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 103 of 228

May 14, 2014

5.3

Driver Status Data

These are the status registers:

Driver

Gateway DB

Address

NTP

65530

MNET Client

65531

MNET Server

65532

IEC-61850

65533

Reboot

65534


Driver Status Register’s possible values are:
1 = Ok

0 = Failed or Driver startup/restart is occurring

61850 IED status registers:

Gateway DB

Address

Description

65450

Node 0 status

65451

Node 1 status

65452

Node 2 status

...

...

65494

Node 44 status

65495

Reconnect count

Possible values are:

1 - Node connected

0 - Node initializing

-1 - Node disconnected. It may take up to 15 minutes to show this, and will first
show as “-2”.
-2

– Node in error

5.3.1 Rebooting the Gateway

If you need to reboot the ProSoft gateway, there are a few ways to do it:
 Disconnect and reconnect power from the gateway.
 From the PLC or generic

Modbus device, write to the gateway’s address

65535 and it will reboot

 From the webpage on the ProSoft gateway, use the Reboot Gateway feature

Advertising