ProSoft 61850 Configuration Manager

PLX8x-MNET-61850 ♦ Communication Gateway

User Manual

Modbus TCP/IP to IEC 61850

Page 44 of 228

ProSoft Technology, Inc.

May 14, 2014

IEC 61850 GOOSE

Map the Generic Object Oriented Substation Event (GOOSE) message that the
IED will produce, and that the ProSoft gateway will send to the PLC. This will be
a broadcast movement of data. GOOSE messages are based upon a DATA-
SET. An entire GOOSE message must fit in one Ethernet packet.

According to the IEC 61850 Standard, GSEControl information is only allowed in
the logical node LLN0.

The right-hand side of the window automatically populates with one row for each
Data Attribute in that DATA-SET when the GOOSE DATA-Set is dragged and
dropped to the right-hand side.

The ProSoft gateway supports multiple Data Attributes in a GOOSE DATA-SET.

The gateway allows mapping of the entire DATA-SET for GOOSE, or mapping
only the data attributes of interest.

On the right-hand side of the window, all of the columns of data are automatically
filled in:
61850

P

ATH

- You will notice that ProSoft 61850 Configuration Manager

places a prefix of GOOSE into this column. The remainder is the standard
IEC-61850 path as would be expected.