ProSoft Technology PLX8X-MNET-61850 User Manual

Page 149

Advertising
background image

PLX8x-MNET-61850 ♦ Communication Gateway

Reference

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 149 of 228

May 14, 2014

6.4.2 DATA-SET

The DATA-SETs are important for Buffered Report Control Blocks (BRCBs),
Unbuffered Report Control Blocks (URCBs), and GOOSE Control Blocks. These
Report Control Blocks (RCBs) reference a DATA-SET to know what data to send
to the IEC 61850 Client. For some IEDs, the DATA-SET may be:
 Static
 Dynamic
 Optionally not reported in its entirety
This varibility is based on features of specific IEDs. ProSoft 61850 Configuration
Manager does not allow the user to dynamically create a DATA-SET on the IED.

The definition of a DATA-SET is the group of Data Attributes that make up the
DATA-SET. DATA-

SETs (if they exist) are defined as part of the IED’s

configuration, as provided by the IED manufacturer.

The assignment of the DATA-SET to a BRCB, URCB, or GOOSE Control Block
is set on the IED. These DATA-SET definitions are currently outside the scope of
the gateway. See the BRCB, URCB, and GOOSE sections of this document to
understand how DATA-SETs are used by the gateway, and for examples.

{This diagram has been taken directly from the IEC 61850 Standards document.}

6.4.3 Report Control Block

This section describes the gateway’s implementation of IEC 61850-7-2 Clause
14: REPORT-CONTROL-BLOCK.

Log and logging is not supported at this time.

The Report Control Block (RCB) is made available to the user through ProSoft
61850 Configuration Manager. The parsing of the CID/SCD file will discover the
ReportControl element, which will be unique within the Logical Node (LN).
ProSoft 61850 Configuration Manager will present the ReportControl items to the
user, for the user to map to the other protocol in the gateway, if required or
desired.