5.5

ProSoft 61850 Configuration Manager Diagnostics

5.5.1 IEC 61850 Client Diagnostics

The following sets of IEC 61850 Client diagnostics data are available from the
ProSoft gateway:
 Configuration Settings
 Driver Status
 Remote Node Config
 Remote Node Status
 Report Status
 GOOSE Subscription Status

Configuration Settings

Setting

Description

TimeOut

The value in seconds for the command to timeout from a
request

GOOSE Support

TRUE or FALSE value, indicating if GOOSE messaging is
supported and configured on the gateway

Sampled Values Support

TRUE or FALSE value, indicating is Sampled Values is
supported and configured on the gateway

Number of Remote Addresses

The count of remote addresses present in the current
operating configuration of the gateway, in the IEC-61850
driver

Reports Configured

TRUE or FALSE value in driver indicating if reports are
currently configured in the IEC-61850 driver

Number of Commands

The total count of Read and Write commands present in the
current operating configuration of the IEC-61850 driver

Number of GOOSE Subscriptions

The total count of GOOSE subscriptions present in the
current operating configuration of the IEC-61850 driver

Number of Reports Configured

The total count of reports (Buffered and Unbuffered) present
in the current operating configuration of the IEC-61850
driver