PLX8x-MNET-61850 ♦ Communication Gateway
Example Configurations
Modbus TCP/IP to IEC 61850
User Manual
ProSoft Technology, Inc.
Page 71 of 228
May 14, 2014
e The data that will be read from the IED and sent to the PLC needs to be
mapped. This will be a MMS (IEC-61850-8-1) data movement. In this
example, one Data Attribute will be moved. Double-click or right-click and
choose C
ONFIGURE
on IEC 61850 icon, an IEC 61850 Mapping Tool
window will appear.
f
In the tree view on the left, expand (click) the + sign. This shows the
Logical Devices (notice the little LD in the icon) in the IED.
g Expand (click) the + sign on one of the Logical Devices in the IED to see
the Logical Nodes (notice the little LN in the icon) within it.
h Choose the MMXU1 data to read the voltage on phase 1.
i
Locate the Data Attribute to read from the IED.