ProSoft 61850 Configuration Manager

PLX8x-MNET-61850 ♦ Communication Gateway

User Manual

Modbus TCP/IP to IEC 61850

Page 28 of 228

ProSoft Technology, Inc.

May 14, 2014

Drag and drop the IEDs (not the CID or SCD file name, but the IED inside it) over
to the Network View section to configure them to communicate with the ProSoft
gateway. If you are familiar with looking at the contents of CID, SCD, and ICD
files, it may be useful to use the D

ISPLAY

/E

DIT

option, shown here.

Normally this feature will not be used to alter configured files. It is a handy
reference tool if you are familiar with these files, and want to look up something
in it. The IED has its own configuration software, and that software should be
used to configure the IED.

The other two menu options on the context menu with Display/Edit are:

A

DD

IED: This is the same action as choosing A

DD

IED from right-mouse-clicking

on IEC

61850

C

ONFIGURATIONS

.

U

PDATE

IED: This is used to import newer versions of previously loaded IEC

configuration files. For additional details see Updating a CID File.