ProSoft Technology PLX8X-MNET-61850 User Manual

Page 53

Advertising
background image

PLX8x-MNET-61850 ♦ Communication Gateway

ProSoft 61850 Configuration Manager

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 53 of 228

May 14, 2014

 A separate Tag Names file (.CSV), which lists tag names in a comma-

separated value file format

Quantum processors with Ethernet ports can use the Function Block in the .xfm
file only if the processor is using firmware version of 2.6 or later. But, if you use a
NOE card for Ethernet connection between a Modicon PLC and the ProSoft
gateway, the processor firmware version does not matter.

PLC Map Properties

The following general properties are available. Not all properties are used for all
four Modbus device types:

Property

Description

Name

Name of the PLC, this is informational only.

IP

The IP address of the target device being accessed by the gateway’s
Modbus TCP/IP Client commands. Format is xxx.xxx.xxx.xxx

Netmask

This is the setting for the TCP/IP network hosting the ProSoft Gateway.
The default value of 255.255.255.0 will work for many installations, or
you can ask your network administrator for the correct setting.

Gateway

The gateway address is the address of the computer, server, or router
that passes traffic between a workstation on the local subnet to devices
on different subnets or remote networks.

PLC Read Start Register
(%MW)

This is the starting address in the PLC to which the ProSoft gateway
will write. (The gateway writes with Modbus Function Code 16.)
Entering a value of 1 means the gateway will write to PLC starting
address of 40001. The default value is 1

PLC Write Start Register
(%MW)

This is the starting address in the PLC from which the ProSoft gateway
will read. Entering a value of 1000 means the gateway will read from
the PLC starting at address %MW1000 (41000). The default value is
1000

NOE Slot No (1-15)

Note:

If you’re using a Schneider Electric NOE Ethernet module in the

rack, rather than the processor's built-in Ethernet port (available on
certain processors), then check this checkbox.

NOE Slot No (1-

15): If using an NOE Ethernet module, enter the NOE’s

slot number in the rack here. This is informational only.

Minimum Command
Delay

This is the minimum number of milliseconds between commands. Valid
values range from 0 to 32767. The default value is 0. This parameter
can be used to delay all commands sent to the Modbus TCP/IP Server
(PLC) to avoid "flooding" commands on the network. This parameter
does not affect retries of a command as they will be issued when failure
is recognized.

Response Timeout

This is the time in milliseconds that the Modbus TCP/IP Client will wait
before re-transmitting a command if no response is received from the
addressed Server. Valid values range from 0 to 65535. The default
value is 1000. The value to use depends upon the type of
communication network used, and the expected response time of the
slowest device on the network.

Advertising