Modbus Communication Error Codes

Code

Description

-1

CTS modem control line not set before transmit

-2

Timeout while transmitting message

-11

Timeout waiting for response after request

253

Incorrect slave address in response

254

Incorrect function code in response

255

Invalid CRC/LRC value in response

MNET Client Specific Errors

Code

Description

-33

Failed to connect to server specified in command

-36

MNET command response timeout

-37

TCP/IP connection ended before session finished

Command List Entry Errors

Code

Description

-40

Too few parameters

-41

Invalid enable code

-42

Internal address > maximum address

-43

Invalid node address (<0 or >255)

-44

Count parameter set to 0

-45

Invalid function code

-46

Invalid swap code

-47

ARP could not resolve MAC from IP (bad IP address, not part of a
network, invalid parameter to ARP routine).

-48

Error during ARP operation: the response to the ARP request did
not arrive to the gateway after a user-adjustable ARP Timeout.

Last Error

Execution Count: Total number of times this command was sent / triggered.