Example Configurations

PLX8x-MNET-61850 ♦ Communication Gateway

User Manual

Modbus TCP/IP to IEC 61850

Page 68 of 228

ProSoft Technology, Inc.

May 14, 2014

Leaving these two fields at their default settings of 1 (read) and 1000 (write)
means:
 The Modbus Client will use Function Code 16 to send data to the PLC

Holding Registers starting at address 40001 (400001 or % MW1, depending
on device and programming software used).

 The Modbus Server will receive data to be mapped to IED Control tags to

from PLC Holding Registers starting at address 41000 (401000 or %MW
1000).

(After working through this example, if you wish to use the example in your own
application, the PLC Read Start Register and PLC Write Start Register values
can be set according to the PLC program settings.)