ProSoft 61850 Configuration Manager

PLX8x-MNET-61850 ♦ Communication Gateway

User Manual

Modbus TCP/IP to IEC 61850

Page 52 of 228

ProSoft Technology, Inc.

May 14, 2014

PLX

S

TART

MB

A

DDRESS

: This is the address in the ProSoft gateway where this

data can be found.

T

AG

N

AME

: This is the tag name for this IEC-61850 Data Attribute, as named

automatically by ProSoft 61850 Configuration Manager, or optionally changed by
the user in the IEC 61850 Mapping Tool window.

S

IZE

: This is the size, in words, of the data. Please see the following chart, giving

the mapping of the IEC-61850 data types to Modbus.

IEC 61850 Data Type

Number of Modbus
Words

Modbus Data Type for
Unity Pro

Size in Unity
Pro

BOOLEAN

1

INT

1

INT8

1

INT

1

INT16

1

INT

1

INT24

2

INT

2

INT32

2

INT

2

INT128

Not Supported

Not Supported

Not Supported

INT8U

1

INT

1

INT16U

1

INT

1

INT24U

2

INT

2

INT32U

2

UDINT

1

FLOAT32

2

REAL

1

FLOAT64

Not Supported

Not Supported

Not Supported

Enum

1

INT

1

Dbpos

1

INT

1

Tcmd

1

INT

1

Quality

1

INT

1

Timestamp

4

INT

4

VisString32

51

INT

51

VisString64

51

INT

51

VisString255

51

INT

51

Octet64

32

INT

32

EntryTime

2

INT

2

Unicode255

51

INT

51

BitString

1

INT

1

Check

1

INT

1

When you choose E

XPORT

P

ROCESSOR

F

ILES

, ProSoft 61850 Configuration

Manager will prompt you for a location for three new files.


 A Variable file (.xsy) , which contains Tag Names and Data Types
 A Function Block file (.xfm), which is only exported for Quantum, Premium, or

M340 device types (not used with the generic Modbus Device option)