PLX8x-MNET-61850 ♦ Communication Gateway

Example Configurations

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 81 of 228

May 14, 2014

b DATA-SET. To configure the ProSoft gateway

to subscribe to the IED’s

GOOSE message, drag and drop the yellow folder showing the GOOSE
name to the right side of the window.

When you drag and drop the GOOSE DATA-SET, the right-hand side of the
window will automatically populate with one row for each Data Attribute in
that DATA-SET.

c Choose M

APPING

/

S

AVE

.

d On the Quantum, Premium, or M340 icon, choose PLC Map View, and

left-click the E

XPORT

P

ROCESSOR

F

ILES

button.

e Go into Unity Pro and import the files.
f

S

AVE

the Project