PLX8x-MNET-61850 ♦ Communication Gateway
Example Configurations
Modbus TCP/IP to IEC 61850
User Manual
ProSoft Technology, Inc.
Page 81 of 228
May 14, 2014
b DATA-SET. To configure the ProSoft gateway
to subscribe to the IED’s
GOOSE message, drag and drop the yellow folder showing the GOOSE
name to the right side of the window.
When you drag and drop the GOOSE DATA-SET, the right-hand side of the
window will automatically populate with one row for each Data Attribute in
that DATA-SET.
c Choose M
APPING
/
S
AVE
.
d On the Quantum, Premium, or M340 icon, choose PLC Map View, and
left-click the E
XPORT
P
ROCESSOR
F
ILES
button.
e Go into Unity Pro and import the files.
f
S
AVE
the Project