PLX8x-MNET-61850 ♦ Communication Gateway

Diagnostics and Troubleshooting

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 121 of 228

May 14, 2014

5.5.4 SNTP/NTP

Status:

Time from SNTP/NTP server: This will show the time retrieved by the
SNTP/NTP server.

Poll Count:

Clock Update Count: This will display the number of times the ProSoft
gateway

’s clock has been updated.

Error Count: This is the number of unsuccessful times the ProSoft gateway has
attempted to reach the SNTP/ NTP Server.

Configuration Settings
U

PDATE RATE IN

M

INUTES

: How frequently the time is synchronized via

SNTP/NTP. This is a configured value that is set on the ProSoft Gateway
Configuration
window, in the SNTP/NTP Update Time field.

S

ERVER

A

DDRESS

: The IP address or domain name for the SNTP/NTP server.

This is a configured value that is set on the ProSoft Gateway Configuration
window, in the SNTP/NTP Address field.

Driver Status
S

TATUS

: This is the result of the latest poll, and is one of OK or Error

retrieving time from SNTP/NTP server.

P

OLL

C

OUNT

: This is the number of update attempts (at the configured

frequency) since startup (unsigned long rolls over at 4 billion plus). If Poll
Count
is zero (before first attempt, or configured update time is 0 for never
poll
) Status is OK.