ProSoft Technology PLX8X-MNET-61850 User Manual

Page 119

Advertising
background image

PLX8x-MNET-61850 ♦ Communication Gateway

Diagnostics and Troubleshooting

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 119 of 228

May 14, 2014

Server Status

MBAP Server: Number of connections to the gateway MBAP Server.

Requests: Total count of requests received for data.

Responses: Total count of responses sent.

Errors Received: Total number of errors received.

Errors Sent: Total number of errors sent.

Current Error: The current error number.

Exception Code

MODBUS name

Description

01

Illegal Function Code

The function code is unknown by the server

02

Illegal Data Address

Dependent upon the request

03

Illegal Data Value

Dependent on the request

04

Server Failure

The server failed during the execution

05

Acknowledge

The server accepted the service invocation but the
service requires a relatively long time to execute.
The server therefore returns only an
acknowledgement of the service invocation receipt.

06

Server Busy

The server was unable to accept the MB Request
PDU. The Client application has the responsibility
of deciding if and when to re-send the request.

1 = communicating, 0 = not communicating.

Current Error

The following Current Error diagnostics data is available from the gateway:
 Standard Modbus Protocol Errors
 Module Communication Error Codes
 MNET Client Specific Errors
 Command List Entry Errors

Standard Modbus Protocol Errors

Code

Description

1

Illegal function

2

Illegal Data Address

3

Illegal Data Value

4

Failure in Associated Device

5

Acknowledge

6

Busy, Rejected Message

Advertising