ProSoft Technology PLX8X-MNET-61850 User Manual

Page 140

Advertising
background image

Reference

PLX8x-MNET-61850 ♦ Communication Gateway

User Manual

Modbus TCP/IP to IEC 61850

Page 140 of 228

ProSoft Technology, Inc.

May 14, 2014

6.1.3 Specifications - IEC 61850 Client

Supports up to

20 IEDs

Send commands from the PLC to the IED using Control Types
o

Direct-with-normal-security

o

Select Before Operate (SBO)-with-normal-security

o

Direct-with-enhanced-security

o

Select Before Operate (SBO)-with-enhanced-security

ACSI Basic Conformance

SCSMs supported

SCSM: IEC 61850-8-1 used

ACSI Model Conformance

Reporting

Buffered Report Control Block (BRCB)
Unbuffered Report Control Block (URCB)

GOOSE:

entryID, DataReflnc

Control

Direct-with-normal-security
SBO-with-normal-security
Direct-with-enhanced-security
SBO-with-enhanced-security

Logical Nodes

IEC 61850 Logical Nodes, including Logical
Nodes for Hydro Power Plants and Logical
Nodes for Wind Power Plants

Configurable Parameters

MMS Command Delay

Status Data

Status available per node
Report and GOOSE status available
High-level status data available from Modbus
TCP/IP Client ( for example PLC)

6.1.4 Specifications

–SNTP/NTP Client

The gateway supports a Simple Network Time Protocol (SNTP/NTP) client
service that can synchronize the gateway’s time by periodic updates to a Co-
ordinated Universal Time (UTC) system. The user can configure the SNTP/NTP
server details in ProSoft 61850 Configuration Manager. The resolution of the time
is in milliseconds (ms).

Configurable Parameters:

SNTP/NTP server synchronization rate (in minutes)
SNTP/NTP Address

Advertising