Updating a cid file – ProSoft Technology PLX8X-MNET-61850 User Manual

Page 87

Advertising
background image

PLX8x-MNET-61850 ♦ Communication Gateway

Example Configurations

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 87 of 228

May 14, 2014

3.8

Updating a CID File

Changes may need to be made to the CID, ICD, or SCD files after the ProSoft
gateway configuration has been setup.

Perhaps on your IED you have modified a DATA-

SET that’s used by the ProSoft

gateway, or added or removed some Data Attributes. When you make changes
like this, its easy to update ProSoft 61850 Configuration Manager with this
information.

Click on the CID,

SCD,

OR

ICD filename in the Device View section of ProSoft

61850 Configuration Manager. Choose U

PDATE

IED.


It will prompt you to browse for the new file. Oftentimes you’ll use the exact same
filename as you used when you imported the file into ProSoft 61850
Configuration Manager the first time.