PLX8x-MNET-61850 ♦ Communication Gateway

ProSoft 61850 Configuration Manager

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 33 of 228

May 14, 2014

C

ONNECTION

T

IMEOUT

: 0 to 1200 seconds. This is the number of seconds the

Server will wait to receive new data. If the Modbus TCP/IP Server does not
receive any new data during this time, it will close the Ethernet socket
connection. The default value is 60.

The gateway supports multiple MNET servers and MBAP servers.

E

NCAPSULATED

M

ODBUS

: This is the number of Modbus TCP/IP Client devices

that will communicate with the gateway using TCP/IP Service Port 2000. These
are devices that use Modbus RTU serial-style message structures enclosed in an
Ethernet wrapper.

MBAP

: This is the number of Modbus TCP/IP Client devices that will

communicate with the gateway using Schneider Electric MBAP-style messages
on TCP/IP Service Port 502.

2.2.1 Modbus TCP/IP Client and Server - Lookup