ProSoft Technology PLX8X-MNET-61850 User Manual

Page 156

Advertising
background image

Reference

PLX8x-MNET-61850 ♦ Communication Gateway

User Manual

Modbus TCP/IP to IEC 61850

Page 156 of 228

ProSoft Technology, Inc.

May 14, 2014

(This table has been taken directly from the IEC 61850 Standard document)

ctlVal

This must be set for:
 SPC (Single Point Control)
 DPC (Double Point Control)
 INC (Controllable Integer Status)
 BSC (Binary Controlled Step Position Information)
 ISC (Integer Controlled Step Position Information
 CDCs (Common Data Classes)

(This table has been taken directly from the IEC 61850 Standard document)

setMag
 This must be set by the user for APC (Controllable Analogue Set Point

Information) CDC.

operTm
 The PLC user sends a command with operate time to the gateway, and the

gateway uses time activated control, e.g. it sends the time of operation to the
IED. The IED needs to support the time activated control.

origin.orCat
 The orCat could have these values. The value depends upon the role of the

PLC. E.g. if the PLC is a station control, then this value will never change.

not-supported

orCat is not supported

bay-control

Control operation issued from an operator using a Client located at bay level

station-control

Control operation issued from an operator using a Client located at station
level

remote-control

Control operation from a remote operater outside the substation (for example
network control center)

automatic-bay

Control operation issued from an automatic function at bay level

automatic-station Control operation issued from an automatic function at station level

automatic-remote Control operation issued from a automatic function outside of the substation

maintenance

Control operation issued from a maintenance/service tool