Installation Considerations

1. There are distance limitations for Wiegand and RS-485 communications. Please note:

Wiegand interface:

Recommended Wiegand cable:

Wiegand cable (a twisted pair of 24 AWG wires)

100 meters (328.1 feet) for GV-AS2110 / 2120 / 4110 / 8110

30 meters (98.43 feet) for other GV-AS Controllers

RS-485 interface:

600 meters (1968.50 feet)

Recommended RS-485 cable:

standard 485 cable (a twisted pair of 24 AWG wires)

2. GV-ASManager software is used to manage GV-AS / GV-EV Controllers. There is a limit
for the number of controllers connected to GV-ASManager based on communication modes.

Through network connection

, up to 1000 GV-AS / GV-EV Controllers can connect to

GV-ASManager.

Through RS-485 connection

, up to 16 GV-AS100 / 110 / 120 Controllers can connect

to the same COM port on a computer running GV-ASManager.


3. When presenting cards to GeoVision readers and the built-in readers of GV-AS100 / 1010
/ 110 / 1110 / 120, make sure only one card is presented at a time to avoid frequency
interference.

Note:

1. For RS-485 connection between GV-AS Controllers and readers, user additional

power for the readers when the distance ranges from 30.48 ~ 600 meters (100 ~
1968.50 ft). There is no need to use additional power when the distance is within
30.48 meters (100 ft).

2. For GV-AS100 / 2110 / 2120 / 4110 / 8110, it is highly recommended to replace the

button cell battery included on the circuit board annually.