GeoVision GV-AS2120 IP Control Panel User Manual

Page 93

Advertising
background image

GV-AS210 / 2110 / 2120 Controller

91

4

Note:

It is highly recommended that you connect the fire alarm button to the 12V power

port and electromagnetic lock directly, as the figure below shows. This enables all the
associated doors to be triggered even if your GV-AS21 series Controller behaves
abnormally when a fire condition occurs.

GND

GND

12V

12V

IN1
IN2
IN3
IN4

INCOM
INCOM

NO

COM

NC

NO

COM

NC

Power

INPUT

OUTPUT

Exit

Button

1

2

NC

NO

COM

Fire Alarm

Button

Electromagnetic

Lock

+

-