C” group: intelligent terminal functions, Input terminal configuration, C” group: intelligent terminal functions 3–34 – Hitachi SJ100 User Manual

Page 106

Advertising
background image

“C” Group: Intelligent Terminal Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–34

“C” Group: Intelligent Terminal Functions

The six input terminals [1], [2], [3], [4], [5], and [6] can be configured for any of 19
different functions. The next two tables show how to configure the six terminals. The
inputs are logical, in that they are either OFF or ON. We define these states as OFF=0,
and ON=1.

The inverter comes with default options for the six terminals. These default settings are
initially unique, each one having its own setting. Note that European and US versions
have different default settings. You can use any option on any terminal, and even use the
same option twice to create a logical OR (though usually not required).

NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a
thermistor device when the PTC function (option code 19) is assigned to that terminal.

Input Terminal Configuration

Functions and Options –The function codes in the following table let you assign one of
nineteen options to any of the six logic inputs for the SJ100 inverters. The functions
C_01through C_06 configure the terminals [1] through [6] respectively. The “value” of
these particular parameters is not a scalar value, but it is a discrete number that selects
one option from many available options.

For example, if you set function C_01=00, you have assigned option 00 (Forward Run)
to terminal [1]. The option codes and the specifics of how each one works are in
Chapter 4.

“C” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

C_01 Terminal [1] function

Select terminal [1] function,
18 options (see next section)

00

[FW]

00

[FW]

00

[FW]

IN-TM 1 FW

C_02 Terminal [2] function

Select terminal [2] function,
18 options (see next section)

01

[RV]

01

[RV]

01

[RV]

IN-TM 2 RV

C_03 Terminal [3] function

Select terminal [3] function,
18 options (see next section)

02

[CF1]

16

[AT]

02

[CF1]

IN-TM 3 AT

C_04 Terminal [4] function

Select terminal [4] function,
18 options (see next section)

03

[CF2]

13

[USP]

03

[CF2]

IN-TM 4 USP

C_05 Terminal [5] function

Select terminal [5] function,
19 options (see next section)

18

[RS]

09

[2CH]

09

[2CH]

IN-TM 5 2CH

C_06 Terminal [6] function

Select terminal [6] function,
18 options (see next section)

09

[2CH]

18

[RS]

18

[RS]

IN-TM 6 RS