“B” Group: Fine Tuning Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–26

WARNING: When parameter B_12, level of electronic thermal setting, is set to device
FLA rating (Full Load Ampere nameplate rating), the device provides solid state motor
overload protection at 115% of device FLA or equivalent. Parameter B_12, level of
electronic thermal setting, is a variable parameter.

NOTE: For inverter models 005NFE, 011NFE, and 030HFE, the thermal value is less
than the rated amperes (is the same as models 004NFE, 007NFE, and 040HFE respec-
tively). Therefore, be sure to set the electronic thermal overload according to the actual
motor driven by the particular inverter.

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

B_12 Level of electronic

thermal setting

Set a level between 50% and
120% for the rated inverter
current.

Rated current for each

inverter model

*See note

A

E-THM LVL 03.00A

B212 Level of electronic

thermal setting, 2nd
motor

Set a level between 50% and
120% for the rated inverter
current.

Rated current for each

inverter model

*See note

A

2E-THMLVL 03.00A

B_13 Electronic thermal

characteristic

Select from two curves, option
codes:
00... Reduced torque
01... Constant torque

01

01

00

E-THM CHAR CRT

B213 Electronic thermal

characteristic, 2nd
motor

Select from two curves, option
codes:
00... Reduced torque
01... Constant torque

01

01

00

2E-THMCHAR CRT

Advertising