Electronic thermal overload alarm setting – Hitachi SJ100 User Manual

Page 97

Advertising
background image

SJ100 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–25

Electronic Thermal Overload Alarm Setting

The thermal overload detection protects the
inverter and motor from overheating due to
an excessive load. It uses a current/inverse
time curve to determine the trip point.

First, use B_13 to select the torque charac-
teristic that matches your load. This allows
the inverter to utilize the best thermal
overload characteristic for your application.

The torque developed in a motor is directly
proportional to the current in the windings,
which is also proportional to the heat generated (and temperature, over time). Therefore,
you must set the thermal overload threshold in terms of current (amperes) for parameter
B_12. The range is 50% to 120% of the rated current for each inverter model. If the
current exceeds the level you specify, the inverter will trip and log an event (error E05) in
the history table. The inverter turns the motor output OFF when tripped. Separate
settings are available for the second motor (if applicable) as shown in the following
table.

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

B_01 Selection of automatic

restart mode

Select inverter restart method,
four option codes:
00... Alarm output after trip,
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.

00

00

00

IPS POWR ALM

B_02 Allowable under-

voltage power failure
time

The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.

1.0

1.0

1.0

sec.

IPS UVTIME 01.0s

B_03 Retry wait time before

motor restart

Time delay after under-voltage
condition goes away, before
the inverter runs motor again.
Range is 0.3 to 100 seconds.

1.0

1.0

1.0

sec.

IPS WAIT 001.0s

Output frequency

Constant torque

Reduced

torque

B_13 = 01

B_13 = 00

Torque

5

20

60

120

Hz

100%

80%

60%

0