Wire the inverter output to motor, Logic control wiring – Hitachi SJ100 User Manual

Page 62

Advertising
background image

Step-by-Step Basic Installation

In

v

e

rt

er Mounting

and Installation

2–18

Wire the Inverter Output to Motor

Step 7: The process of motor selection is beyond the scope of this manual. However, it
must be an AC induction motor with three phases. It should also come with a chassis
ground lug. If the motor does not have three power input leads, stop the installation and
verify the motor type. Other guidelines for wiring the motor include:

• Use an inverter-grade motor for maximum motor life (1600V insulation).

• For standard motors, use the AC reactor accessory if the wiring between the inverter

and motor exceeds 10 meters in length.

Simply connect the motor to the terminals
[U/T1], [V/T2], and [W/T3] as shown to the
right. This is a good time to connect the
chassis ground lug on the drive as well. The
motor chassis ground must also connect to
the same point. Use a star ground (single-
point) arrangement, and never daisy-chain the
grounds (point-to-point).

Use the same wire gauge on the motor and
chassis ground wiring as you used on the
power input wiring in the previous step. After
completing the wiring:

• Check the mechanical integrity of each

wire crimp and terminal connection.

• Replace the housing partition that covers

access to the power connections.

• Close the main door and secure the reten-

tion screw firmly.

Logic Control Wiring

After completing the initial installation and powerup test in this chapter, you may need
to wire the logic signal connector for your application. For new inverter users/applica-
tions, we highly recommend that you first complete the powerup test in this chapter
without adding any logic control wiring. Then you will be ready to set the required
parameters for logic control as covered in Chapter 4, Operations and Monitoring.

7

To Power

Supply

To Motor

To Chassis

Ground

Advertising