Analog and Digital Monitor Output

Oper

ations

and Monitor

ing

4–34

TIP: When using the analog meter for monitoring, adjust the meter so it has a zero
reading when the [FM] output is zero. Then use scale factor B_81 to adjust the [FM]
output so the maximum frequency in the inverter corresponds to a full-scale reading on
the meter.

The following accuracy notes apply for PWM monitor outputs:

• The monitor accuracy for frequency monitoring after adjustment is about

±5%.

Depending on the motor, the accuracy may exceed this value.

• The monitor display accuracy for current (normally

± 20%, depending on the

connected motor’s characteristics) can be improved by adjusting parameter B_32.

• The accuracy of the current reading is given by the equation:

• If precise current measurement is necessary, use the moving-coil type ammeter

between the inverter and the motor.

PWM Smoothing Circuit – You may also
wish to smooth the PWM signal at the [FM]
terminal and convert it to an analog signal.
The [FM] terminal will then generate a
relatively stable DC analog voltage that
represents the output value. To do this, use
the circuit shown to the right. Note the
output impedance of the circuit is at least
82k

Ω, so the monitoring device needs an

input impedance of 1M

Ω or greater. Other-

wise, the impedance of the smoothing
circuit will cause a non-linearity in the reading.

FM Signal Type

The frequency-modulated output at terminal [FM] varies its frequency with the inverter
output frequency (C_23=02). The multiplier is 10, such that the maximum [FM] signal
frequency is 10 x 360 = 3.6 kHz, or 10 times the inverter’s maximum output frequency.
The signal at [FM] uses the parameter A_04 Maximum frequency setting. For example, if
A_04 = 60 Hz, then the maximum signal value at [FM] will be 10 x 60 = 600 Hz. This
frequency is digitally controlled for accuracy, and does not use the B_81 gain setting
when C_23=02 (frequency modulation selection).

Imc Im

Ir

----------------------

100

×

20%

±

Im = Inverter output current (measured)

Imc = Monitor display current

Ir = Inverter rated current

+

12 11

L

H O OI

FM CM2

33k

82k

1

µF Volts

+

+

See I/O specs on page

4–6

.

T

1

[FM] Output value 10

×

---------------------------------------------------------

=

Selects FM type output

[FM]

C_23 = 02

50% fixed duty cycle

10V

0V

t

T

[FM] Output value

1

T 10

Ч

---------------

=