Signal Ratings

Detailed ratings are in

“Specifications of Control and Logic Connections” on page 4–6

.

Signal / Contact

Ratings

Built-in power for inputs

24VDC, 30 mA maximum

Discrete logic inputs

27VDC maximum

Discrete logic outputs

50mA maximum ON state current, 27 VDC maximum OFF state voltage

PWM (analog/digital) output

0 to 10VDC, 1 mA, PWM and 50% duty digital

Analog input, current

4 to 19.6 mA range, 20 mA nominal

Analog input, voltage

0 to 9.6 VDC range, 10VDC nominal, input impedance 10 k

+10V analog reference

10VDC nominal, 10 mA maximum

Alarm relay contacts

250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min.
30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.
5 VDC, 100mA min.