background image

Parameter Settings for Keypad Entry

Appendix B

B–6

Fine Tuning Functions

“B” Group Parameters

Default Setting

User

Setting

Func.

Code

Name

-FE

(Europe)

-FU

(USA)

–FR

(Japan)

B_01

Selection of automatic restart
mode

00

00

00

B_02

Allowable under-voltage power
failure time

1.0

1.0

1.0

B_03

Retry wait time before motor
restart

1.0

1.0

1.0

B_12

Level of electronic thermal
setting

Rated

current for

each

inverter

Rated

current for

each

inverter

Rated

current for

each

inverter

B212

Level of electronic thermal
setting, 2nd motor

Rated

current for

each

inverter

Rated

current for

each

inverter

Rated

current for

each

inverter

B_13

Electronic thermal characteristic

01

01

00

B213

Electronic thermal characteristic,
2nd motor

01

01

00

B_21

Overload restriction operation
mode

01

01

01

B_22

Overload restriction setting

Rated

current x

1.25

Rated

current x

1.25

Rated

current x

1.25

B_23

Deceleration rate at overload
restriction

1.0

1.0

1.0

B_31

Software lock mode selection

01

01

01

B_81

[FM] terminal analog meter
adjustment

80

80

80

B_82

Start frequency adjustment

0.5

0.5

0.5

B_83

Carrier frequency setting

5.0

5.0

12.0

B_84

Initialization mode (parameters
or trip history)

00

00

00

B_85

Country code for initialization

01

02

00

B_86

Frequency scaling conversion
factor

1.0

1.0

1.0

B_87

STOP key enable

00

00

00

B_88

Restart mode after FRS

00

00

00

Advertising