SJ100 Inverter

xiii

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the
table below.

Wire Connectors

WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.

Input

Voltage

Motor Output

Inverter Model

Wiring Size

Range (AWG)

Torque

kW

HP

ft-lbs

(N-m)

200V

0.2 1/4

SJ100-002NFE/NFU

16

0.6

0.8

0.4

1/2

SJ100-004NFE/NFU

0.55

3/4

SJ100-005NFE

0.75

1

SJ100-007NFE/NFU

14

0.9

1.2

1.1

1 1/2

SJ100-011NFE

1.5

2

SJ100-015NFE/NFU

12

2.2

3

SJ100-022NFE/NFU

10

3.7

5

SJ100-037LFU

12

5.5

7 1/2

SJ100-055LFU

10

1.5

2.0

7.5

10

SJ100-075LFU

8

400V

0.4

1/2

SJ100-004HFE/HFU

16

0.9

1.2

0.75

1

SJ100-007HFE/HFU

1.5

2

SJ100-015HFE/HFU

2.2

3

SJ100-022HFE/HFU

3.0

4

SJ100-030HFE

14

4.0

5

SJ100-040HFE/HFU

5.5

7 1/2

SJ100-055HFE/HFU

12

1.5

2.0

7.5

10

SJ100-075HFE/HFU

Cable

Terminal (ring lug)

Cable support