Circuit breaker and fuse sizes, Motor overload protection – Hitachi SJ100 User Manual

Page 15

Advertising
background image

xiv

Circuit Breaker and Fuse Sizes

The inverter’s connections to input power must include UL Listed inverse time circuit
breakers with 600V rating, or UL Listed fuses as shown in the table below.

Motor Overload Protection

Hitachi SJ100 inverters provide solid state motor overload protection, which depends on
the proper setting of the following parameters:

• B_12 “electronic overload protection”

• B212 “electronic overload protection, 2nd motor”

Set the rated current [Amperes] of the motor(s) with the above parameters. The setting
range is 0.5 * rated current to 1.2 * rated current.

WARNING: When two or more motors are connected to the inverter, they cannot be
protected by the electronic overload protection. Install an external thermal relay on each
motor.

Input

Voltage

Motor Output

Inverter Model

Fuse (A)

(UL-rated,

class J, 600V)

kW

HP

200V

0.2 1/4

SJ100-002NFE/NFU

10

0.4

1/2

SJ100-004NFE/NFU

10

0.55

3/4

SJ100-005NFE

10

0.75

1

SJ100-007NFE/NFU

15

1.1

1 1/2

SJ100-011NFE

15

1.5

2

SJ100-015NFE/NFU

20 (single ph.)

15 (three ph.)

2.2

3

SJ100-022NFE/NFU

30 (single ph.)

20 (three ph.)

3.7

5

SJ100-037LFU

30

5.5

7 1/2

SJ100-055LFU

40

7.5

10

SJ100-075LFU

50

400V

0.4

1/2

SJ100-004HFE/HFU

3

0.75

1

SJ100-007HFE/HFU

6

1.5

2

SJ100-015HFE/HFU

10

2.2

3

SJ100-022HFE/HFU

10

3.0

4

SJ100-030HFE

15

4.0

5

SJ100-040HFE/HFU

15

5.5

7 1/2

SJ100-055HFE/HFU

20

7.5

10

SJ100-075HFE/HFU

25

Advertising