Oper ations and monitor ing – Hitachi SJ100 User Manual

Page 128

Advertising
background image

SJ100 Inverter

Oper

ations

and Monitor

ing

4–11

While using the multi-speed capability, you can monitor the current frequency with
monitor function D_01 during each segment of a multi-speed operation.

NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display parame-
ter F_01 or change the value of F_01 while the inverter is in Run Mode (motor running).
If it is necessary to check the value of F_01 during Run Mode, please monitor D_01
instead of F_01.

There are two ways to program the speeds into the registers A_20 to A_35:

1. Standard keypad programming:

a. Select each parameter A_20 to A_35.

b. Press the

key to view the parameter value.

c. Use the

and

keys to edit the value.

d. Use the

key to save the data to memory.

2. Programming using the CF switches. Set the speed by following these steps:

a. Turn the Run command OFF (Stop Mode).

b. Turn each switch ON and set it to Multi-speed. Display the value of F_01 on the

digital operator.

c. Set the desired output frequency by pressing the

and

keys.

d. Press the

key once to store the set frequency. When this occurs, F_01

indicates the output frequency of Multi-speed n.

e. Press the

key once to confirm that the indication is the same as the set

frequency.

f. Repeat operations in 2. a) to 2. e) to set the frequency of other Multi-speeds. It

can be set also by parameters A_20 to A_35 in the first procedure 1. a) to 1. d).

Valid for inputs:

C_01, C_02, C_03, C_04,
C_05, C_06

Required settings:

F_01, A_01 = 02,
A_20 to A_35

Notes:

When programming the multi-speed settings, be
sure to press the Store key each time and then set
the next multi-speed setting. Note that when the key
is not pressed, no data will be set.

When a multi-speed setting more than 50Hz(60Hz)
is to be set, it is necessary to program the maximum
frequency A_04 high enough to allow that speed.

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

1

2

3

4

5

6

L

P24

Example (some CF inputs require input
configuration; some are default inputs—see
page

3–34

):

See I/O specs on page

4–6

.

CF2

CF3

CF4

CF1

(LSB)

(MSB)

FUNC.

1

2

STR

1

2

STR

FUNC.