F” group: main profile parameters, F” group: main profile parameters 3–8 – Hitachi SJ100 User Manual

Page 80

Advertising
background image

“F” Group: Main Profile Parameters

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–8

“F” Group: Main Profile Parameters

The basic frequency (speed) profile is
defined by parameters contained in the “F”
Group as shown to the right. The set
running frequency is in Hz, but accelera-
tion and deceleration are specified in the
time duration of the ramp (from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the keypad
Run key produces a FWD or REV command. This parameter does not affect the intelli-
gent terminal [FWD] and [REV] functions, which you configure separately.

Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the
main profile. Accel and decel values for an alternative profile are specified by using
parameters Ax92 through Ax93. The motor direction selection (F_04) determines the
direction of rotation as commanded only from the keypad. This setting applies to any
motor profile (1st or 2nd) in use at a particular time

Output

frequency

F 01

F 02

F 03

t

0

“F” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

F_01

Output frequency
setting

Standard default target
frequency that determines
constant motor speed,
range is 0 to 360 Hz

0.0

0.0

0.0

Hz

TM 000.0 0.0Hz

F_02

Acceleration (1) time
setting

Standard default acceleration,
range is 0.1 to 3000 sec.

10.0

10.0

10.0

sec.

ACC 1 0010.0s

F202

Acceleration (1) time
setting, 2nd motor

Standard default acceleration,
2nd motor,
range is 0.1 to 3000 sec.

10.0

10.0

10.0

sec.

2ACC1 0010.0s

F_03

Deceleration (1) time
setting

Standard default deceleration,
range is 0.1 to 3000 sec.

10.0

10.0

10.0

sec.

DEC 1 0010.0s

F203

Deceleration (1) time
setting, 2nd motor

Standard default deceleration,
2nd motor,
range is 0.1 to 3000 sec.

10.0

10.0

10.0

sec.

2DEC1 0010.0s

F_04

Keypad Run key
routing

Two options; select codes:
00... Forward
01... Reverse

00

00

00

INIT DOPE FWD

Advertising