Auto-tuning for Sensorless Vector Control

Oper

ations

and Monitor

ing

4–36

NOTE: During step 11, the motor will make a slight humming sound during the AC and
DC excitation (A and B) steps of the auto-tuning process. This sound is normal.

NOTE: When the SLV control method is selected with A_44, set the carrier frequency
to 2.1 kHz or higher with B_83.

8

A_82 AVR voltage select Select output voltage for motor

200V class: 200/220/230/240
400V class: 380/400/415/440/
460

Voltage setting cannot be greater
than input voltage

9

A_51 DC braking enable Set = 00 to disable DC braking

Default = 00 (disabled)

10

H_01 Auto-tuning

Setting

Set = 01 (full auto-tuning
Set = 02 (partial auto-tuning –
measures resistance and induc-
tance only)

Try using H_01 = 01, if possible.
If application or load interferes
with or prohibits motor rotation,
then use H_01 = 02.

11

Press the RUN key on the
keypad and wait for the test to
complete

The inverter actions are:
A) .. AC excitation (no rotation)
B)... DC excitation (no rotation)
C)... Motor accelerates to 80% of
base frequency, then stops.
D) Motor accelerates to A20
setting frequency, then stops.

12

Interpret results by reading the
display pattern

Auto-tuning process completed
steps A) to D)

Auto-tuning failed at
step A) or B)

13

Reset Inverter by pressing the
Stop/Reset Key

Inverter will display alternating
pattern on the display and return
to parameter menu. Auto-tuning
will be OFF. Make any correc-
tions and start again at step 10.

Step

Parameter

Parameter Setting or Action

Notes

Code

Name