Two-stage Acceleration and Deceleration

When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings (F_02
and F_03) to use the second set of accelera-
tion/deceleration values. When the terminal is
turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F_02 acceleration time 1, and F_03 decelera-
tion time 1). Use A_92 (acceleration time 2)
and A_93 (deceleration time 2) to set the
second stage acceleration and deceleration
times.

In the graph shown above, the [2CH] becomes active during the initial acceleration. This
causes the inverter to switch from using acceleration 1 (F_02) to acceleration 2 (A_92).

Output

frequency

[FW],

[RV]

[2CH]

t

target

frequency

second

initial

1
0

1
0

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

09

2CH

Two-stage Accelera-
tion and Deceleration

ON

Frequency output uses 2nd-stage acceleration
and deceleration values

OFF

Frequency output uses the initial acceleration 1
and deceleration 1 values

Valid for inputs:

C_01, C_02, C_03, C_04,
C_05, C_06

Required settings:

A_92, A_93, A_94=00

Notes:

Function A_94 selects the method for second stage
acceleration. It must be set = 00 to select the input
terminal method in order for the [2CH] terminal
assignment to operate.