SJ100 Inverter

Oper

ations

and Monitor

ing

4–25

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is in
Run Mode. The output logic is active low, and
is the open collector type (switch to ground).

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode
to prevent the negative-going turn-off spike generated by the coil from damaging the
inverter’s output transistor.

[FW],

[RV]

Output

freq.

Run

Signal

start freq.

B 82

t

ON

1
0

1
0

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

00

RUN

Run Signal

ON

when inverter is in Run Mode

OFF

when inverter is in Stop Mode

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

(none)

Notes:

The inverter outputs the [RUN] signal whenever the
inverter output exceeds the start frequency specified
by parameter B_82. The start frequency is the initial
inverter output frequency when it turns ON.

RY

+

12 11

L

H O OI

FM CM2

Example (default output configuration
shown—see page

3–38

):

Inverter output
terminal circuit

See I/O specs on page

4–6

.

RUN