Step-by-Step Basic Installation

In

v

e

rt

er Mounting

and Installation

2–16

Please use the terminal arrangement below corresponding to your inverter model.

NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).

CAUTION: Be sure that the input voltage matches the inverter specifications:
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW)
• Three phase 200 to 230V 50/60Hz (above 2.2kW)
• Three phase 380 to 460 V 50/60Hz

CAUTION: Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.

RB +1

+

L1

L2 N/L3 U/T1 V/T2 W/T3

RB +1

+

L1

L2 N/L3 U/T1 V/T2

RB +1

+

L1

L2 N/L3 U/T1 V/T2 W/T3

–002NFE/NFU, –004NFE/NFU, –005NFE

–007 to 022NFE/NFU, –037LFU, 004 to 040HFE/HFU

–055LFU, –075LFU, 055HFE/HFU, 075HFE/HFU

Jumper

Jumper

Jumper

Chassis

Ground

Chassis

Ground

Chassis

Ground